Answers to the questions customers ask us most, from choosing and fitting a dimmer to curing flicker. Search, or browse by product or topic.

Showing 17 questions about V-Dim Show all questions

Choosing a dimmer

Which dimmer suits your lights, how much lighting it can take, and dimming from more than one switch.

How many lamps can my dimmer control?

Add up the wattage of all the lamps the dimmer controls: the number of lamps times the watts printed on each. The total must not be more than the maximum load per gang on the dimmer's label and data sheet. For example, 8 LED downlights of 5W each add up to 40W.

DimmerLoad per dimmer (gang)
V-Pro0-120W or 0-300W, no minimum load
V-Pro Multiway120W (master dimmers 100W), no minimum load
V-Pro Micro160W of dimmable LED
V-Com0-100W, 0-180W or 15-180W (the first figure is the minimum)
V-Dim (halogen)60-400W, or 40-250W on 2-gang dimmers

With low voltage lighting, add up the VA ratings of the transformers, not the wattage of the bulbs.

Copy link and share

Is there a minimum load? Can I dim just one LED lamp?

V-Pro, V-Pro Multiway and V-Pro Micro dimmers have no minimum load, so they can dim a single LED lamp.

Some V-Com dimmers and every V-Dim dimmer have a minimum: it is the first figure of the rating on the label, for example 15-180W. The 0-100W and 0-180W V-Com dimmers have none. Below the minimum the lights may flicker: see flicker caused by too little load.

Copy link and share

Can I mix lighting types on the same dimmer?

VARILIGHT dimmers are not designed to handle mixed lighting types on a single circuit. This includes combining halogen and LED lamps. With halogen lamps being phased out, most installations now use only dimmable LEDs, which ensures optimal performance and reduces the risk of overload.

Copy link and share

Which dimmer should I use for halogen or filament (incandescent) lamps?

While halogen and incandescent bulbs have been largely phased out in the UK and EU, some dimmers are still compatible for legacy installations. V-Dim dimmers suit mains halogen and incandescent lamps. V-Pro and V-Com dimmers can also be used with mains halogen and incandescent lamps, up to their LED maximum load.

For most modern installations we recommend LED lighting with our LED dimmers, which are optimised for LED lighting. We do not recommend V-Dim dimmers for dimmable LEDs, even if de-rated as some manufacturers suggest.

Copy link and share

Can I use a V-Dim dimmer on a 2-way circuit?

Only a push on/off V-Dim dimmer. Rotary on/off dimmers are only suitable for 1-way circuits.

On a 2-way circuit (the same lights controlled by two switches), choose a push on/off dimmer and replace only one of the switches with it. You can only use one push on/off dimmer in a 2-way circuit, and it must be used with a normal switch. When you switch on a push on/off dimmer the lights come on at the level they were at before they were last switched off.

Copy link and share

Can I replace just the dimmer module in my existing plate?

Yes. Our European replacement dimmer modules fit our European dimmer plates. Remove the knob and the front plate, unscrew the nut, take the old module out from the back and fit the new one.

Each module is 64 x 58 x 46mm. Its data sheet shows the instructions and where to buy it.

Copy link and share

Fitting and wiring

Wiring 2-way and multi-way circuits, wall box depths and where to find the instructions. If in doubt, consult a qualified electrician.

Dimmers

Where can I find the instructions or a wiring diagram for my product?

The instruction leaflet, with its wiring diagrams, comes with your product. You can also find every current leaflet on the instruction leaflets page, and leaflets for older and discontinued products on the earlier leaflets page. Where relevant, check the software version and choose the correct leaflet: the software version is on the side of the dimmer module.

We also have a page of wiring diagrams and how-to videos. Every data sheet links to the product's leaflet: type the product code into the search box. If the wiring diagram is not enough, please contact a qualified electrician.

Copy link and share

What do I need to remove before an insulation test?

Dimmers from all of our ranges should be disconnected for the duration of the insulation resistance test. Failing to do so could damage the dimmer and make the product guarantee invalid.

Copy link and share

Parts, finishes and care

Knobs and spare parts, product codes and data sheets, finishes, cleaning and decorating.

Where can I get a replacement dimmer knob?

All our knobs have the same fixing, so they fit every VARILIGHT dimmer. Screwless products need a "pipped" knob, which is slightly raised for spacing. Pipped knobs aren't sold separately: for a replacement, please send us a message or email help@varilight.co.uk and our customer services team will help.

Spare knobs are sold singly or in packs of 10 (the same code with 10 on the end). Click a code for its data sheet, which shows where to buy it:

Copy link and share

Guarantee and older products

The lifetime guarantee, how to claim, and help for products we no longer make.

How do I make a guarantee claim or return a faulty product?

Many problems can be solved without a replacement, so please check the troubleshooting answers first. Then:

  1. Send us a message, or email help@varilight.co.uk, with your purchase details and a description of the problem. Tell us the product code, the batch number (on the plastic moulding at the back of a dimmer), the type and wattage of the lamps it controls, and the fault. Keep your proof of purchase.
  2. The faulty product must be returned: we'll tell you where to send it, to VARILIGHT in the UK or to Varilight Europe Kft in Hungary (both addresses are in the instruction leaflet). Pack it securely with your proof of purchase, your contact details and return address, the type and wattage of the lighting or other load, and the details of the fault.
  3. If the claim is approved, we'll repair or replace the product.

See our lifetime guarantee.

Copy link and share

One dimmer on my multi-gang plate is faulty: can I keep using the others?

Yes. It is perfectly in order to remove a faulty dimmer module from a multi-gang dimmer by pulling off the knob and unscrewing the nut under the knob (and removing the front plate first, on a Screwless product). You will then still have the remaining modules working while we service the faulty one. See how to make a claim.

Copy link and share

Troubleshooting

Dimmers that have stopped working, flicker, buzz or glow, and other problems with installed products.

Not working, or switching off

My dimmer has stopped working: what should I do?

Many faults can be cleared without replacing anything. Switch off at the mains before touching any wiring and, if in doubt, consult a qualified electrician.

  1. Reset the power. Switch the lighting circuit off at the circuit breaker, then back on after a few seconds. An overloaded dimmer switches itself off to protect itself.
  2. Check the load. Add up the wattage of all the lamps on the dimmer (for low voltage lighting, the VA ratings of the transformers). It must not be more than the maximum per gang on the dimmer's label. See how many lamps a dimmer can control.
  3. Changed the bulbs? If you have changed the type of lamp, reset the dimmer to its factory settings: see set up your dimmer.
  4. New installation? Check the wiring against the diagram in the instruction leaflet.
  5. Lights come on but won't dim? See my dimmer won't dim the lights.

If it still doesn't work, the dimmer may be faulty. It is covered by our lifetime guarantee: see how to make a claim. It helps to have the product code, the batch number (printed on the plastic moulding at the back of the dimmer) and the type and wattage of your lamps to hand.

Copy link and share

My dimmer turns the lights on and off but won't dim them

V-Pro and V-Com dimmers: we would advise you to perform the factory reset on the dimmer switch. Instructions are also in the product instruction leaflet and on VARILIGHT TV. If you have performed the factory reset and the lights are still not dimming, please contact Customer Services: send us a message or email help@varilight.co.uk.

Other dimmers: this problem is usually caused when one of the components in the dimmer has failed, usually due to a plasma. Plasmas can be caused when a mains halogen light bulb (e.g. GU10) fails. For this reason we recommend only using good quality mains halogen bulbs from well-known brands. If a dimmer shows this fault it will need to be replaced.

The best type of dimmer to use with mains halogen bulbs is a VARILIGHT V-Plus series dimmer. The rapid on-board overload protection can usually turn the dimmer off so quickly that it survives a spike in the mains supply.

Copy link and share

My lights are switching to a reduced brightness

The usual reason is that the dimmer is overloaded. V-Pro and V-Com dimmers switch off until the overload is removed.

Check the maximum load on the label on the back of the dimmer. Add up the wattage of the lamps it controls; with low voltage lighting, add up the VA ratings of the transformers, not the bulbs. If the total is more than the maximum, use fewer or lower-wattage lamps, or a higher-rated dimmer: see how many lamps a dimmer can control.

Copy link and share

Flickering, buzzing and glowing

My dimmer is causing the lights to flicker (minimum load)

This problem is usually caused when the dimmer is under-loaded.

Check the label on the back of the dimmer, where the minimum and maximum load are printed. Add up the ratings of all the light bulbs the dimmer controls and make sure they are more than the minimum. V-Dim dimmers work best with at least 100W. The 0-100W V-Com has no minimum.

If your lighting load is below the minimum, choose a different dimmer or use bulbs with a higher rating: you can still dim them right down. For dimmable LEDs choose a V-Pro dimmer: V-Pro dimmers have no minimum load.

Copy link and share

My dimmer or my lamps are buzzing

It is quite normal for a dimmer switch to buzz a little. A dimmer is more prone to buzz with certain types of lighting load. If your lighting load is causing your dimmer to buzz excessively, we recommend changing the dimmer for a trailing-edge dimmer. Our V-Pro series trailing-edge dimmers are the quietest running dimmers available.

If the LED lamps themselves buzz while a V-Pro dimmer is on, a component within the lamps is vibrating during operation. Changing the driving mode on the dimmer may improve this. If the lamps continue to buzz after trying the different driving modes, we recommend contacting the LED manufacturer for further advice.

With other brands of dimmable electronic transformer, noise levels may vary depending on the type and quantity of transformers used.

Copy link and share

Is it normal for my dimmer to feel warm?

Yes. It is normal for dimmer switches to feel slightly warm during operation, particularly when they are controlling loads close to their maximum rated capacity. During dimming a small amount of heat is generated, and it is intentionally transferred to the front plate through the dimmer module's heat sink. This helps dissipate heat efficiently and protects the internal electronic components.

Touch and remote dimmers also draw a very small standby current when switched off, so they may feel slightly warm even when off. They have over-temperature protection, and the fire retardant material around the electronics at the back may show some discolouration from moderate temperatures, which is expected in normal operation.

Copy link and share

Still stuck?

Our customer services team will help. To get the quickest answer, tell us the product code, the batch number from the back of the dimmer, and the make, wattage and number of lamps.